VPD-02R Phase Failure and Phase Sequence Relay
♥Constant Voltage Asymmetry (Phase – Neutral 40%)
General :
In three phases system, When phase sequence and phase voltage are
all normal ,the OUT light is turned on , relay contact is energised; When
there is default phase or phase sequence errors,the OUT light is off, the
relay de-energizes its contact.
Phase Failure :
When Default phase,the OUT light is off, the relay de-energizes its contact.

Phase Sequence:
When Phase sequence errors,the OUT light is off, the relay de-energizes its contact.

Voltage Asymmetry:
(asym.% ) ( fixed 40% for phase-neutral )
Phase to neutral asymmetry is fixed 40%. If asymmetry exceeds this value, the OUT light is off and the Relay de-energizes its contact. To return normal state, voltage asymmetry value must be under 15% (hysteresis).

Rated Voltage |
3 phase and 1 neutral(VL-N:230Vac and VL-L:400Vac) |
Operating Range |
(0.8-1.2)xUn Un norminal voltage |
Frequency |
50/60Hz |
Contact Current |
Max.5A/240V |
Power Consumption |
<8VA |
Device Protection Class |
IP20 |
Connector Protection Class |
IP00 |
Ambient Temperature |
-5°c to +50°c |
Connection Type |
Suftace mounted or rail-mounted |
Dimensions |
36*90*60MM |