VPD-04R 230 volt ac under and overvoltage protection relay
Over and Under voltage % Adjustment
Delay time adjustment
1. Applications: Three- phase undervoltage and Overvlotage Protection
2. Gerenal:
Microprocessor controlled. Three or single phase relay is used in systems exposed to over or under voltage, such as command, control or compensation systems and protects devices such as condensers, motors, air conditioners and compressors. It is divided into sub- categories dependingon the voltage adjustment range, on or off start modes.

Un: 200V 50HZ Neutral
4 wires Star Connection Single Phase
Under Volt. 0.7x Un - 0.95x Un Connection Diagram
Over Volt. 1.05xUn - 1.3x Un
1C/O, 2000VA/8A (Cos=1)
Delay: 0.1s - 20s

3. Function Features:
-When three- phase voltage is normal, the 'Out' LED flash seconds. After the fault recovery time,
setting by potentiometer ' Ton', 'Out' LED turns on, and relay is closed.
When any line voltage is overvoltage, overvoltage failure indicator ' › Un' LED flash seconds
Reaching the fault delay time which setting by 'Toff ', relay disconnect; 'Out' LED turn off
and overvoltage failure indicator ' › Un' LED is turn on. If power recover to normal before the
fault delay time, then relay and 'Out' LED are not act, still closed; When voltage value is 1.3
times higher, without delay, relay immediately disconnect, overvoltage failure 'Un' LED turns on.
When any line voltage is undervoltage, undervoltage failure indicator ' › Un' LED flash seconds
Reaching the fault delay time which setting by 'Toff ', relay disconnect; 'Out' LED turn off and
undervoltage failure indicator ' › Un' LED is turn on. If power recover to normal before the fault
delay time, then relay and 'Out' LED are not act, still closed; When undervoltage value is 0.7 times
lower, without delay, relay immediately disconnect, undervoltage failure 'Un' LED turns on.
When the voltage recover from the fault status to normal, the 'Out' LED flash seconds, fault
recover time which is setting by 'Ton' has reached, then the relay close and output, 'Out' LED
turns on; If the overvoltage and undervoltage happen before the reaching of fault recovery time,
'Out' LED are not act, still disconnected; over voltage and under voltage indicator light on.
4. Technical Data:

Measurement and Supply Circuit
|
|
Supply Voltage (Un)
|
220, 230VAC
400 VAC
|
Supply Frequency
|
50HZ
|
Power Consumption (max.)
|
30VA/2W (50HZ.)
|
Measurement Method
|
True RMS
|
Settings
|
|
Over Voltage Setup (Umax.)
|
1,05...1,30x Un (% Scale)
231 ... 286 VAC
420... 520 VAC
|
Under Voltage Setup (Umin..)
|
0,7...0,95 x Un (% Scale)
154... 209 VAC
280... 380 VAC
|
Hysteresis (for Umax. and Umin.)
|
1%x Un
|
Delay-Off (Delay) Toff
|
0.1 ... 20 sec. (›1.3* Un or 0.7*Un, 0.1Sec)
|
Delay-On (Delay) Ton
|
0.1 ... 20 sec.
|
Voltage Adjustment Accuracy
|
±3%
|
Repetition Accuracy (Voltage)
|
±5%
|
Accuracy of the Set Times
|
±5%+100 msec.
|
Repetition Accuracy (Time)
|
±3%
|
Output
|
|
Output type
|
1 inverter, 8A, 250V, 2000VA (Cos= 1)
|
Electrical life
|
10^5
|
Mechanical life
|
10^7
|
Ambient Condition
|
|
Operation Temperature
|
-5℃...+55℃
|
Relative Humidity
|
<%90 ( without condensation)
|
Connection
|
|
Cable cross- section for terminal
Screw-on force
|
4mm2 (12 AWG) standard rigid cable
6mm2 (10 AWG) solid conductor cable
2x2.5mm2 (14 AWG) solid conductor cable
0.5Nm (4.5 in.lbs)
|
Body
|
|
Installation
|
Inside the panel vertically or on the rail
|
Material type
|
Plastic consistent with UL94 VO
|
Protection class
|
IP 20 (for terminal), IP40 (front panel)
|
Dimensions
|
Type PK 28
|
Weight
|
100 gr.
|
Standard
|
|
EN-60255-6
|
Product standard
|
EN-61000-6-2
|
Immunity
|
EN-61000-6-3, EN-61000-6-4
|
Emission
|
Directives / Regulations to be followed
|
|
73/23/ECC
|
LVD
|
89/336 / ECC
|
EMC
|
Isolation
|
|
Isolation voltage (EN 60255-5)
|
400V
|
Isolation Coordination (EN 60255-5)
|
Exceeding Voltage category III
Pollution degree 3
|
Instant Burst Voltage (EN 60255-5)
|
4kV 1.2 / 50 uS
|
Dielectric Resistance (EN 60255-5)
|
2kV AC 50 Hz. 1 minute.
|
Isolation Resistance (EN 60255-5)
|
›500 MOHM / 500 V DC
|